AF09Z-30-01-21 24-60V50/60HZ 20-60VDC Contactor
AF09Z-30-01-21
Extended Product TypeAF09Z-30-01-21
Product ID1SBL136001R2101
EAN3471523113312
Catalog DescriptionAF09Z-30-01-21 24-60V50/60HZ 20-60VDC Contactor
Long Description
AF09Z contactors are used for controlling power circuits up to 690 V AC and 220 V DC. They are mainly
used for controlling 3-phase motors, non-inductive or slightly inductive loads. AF..Z contactors include an
electronic coil interface accepting a wide control voltage Uc min. ... Uc max. Only four coils cover control
voltages between 24...250 V 50/60 Hz or 12...250 V DC. AF..Z contactors can manage large control voltage
variations. One coil can be used for different control voltages used worldwide without any coil change. AF..Z
contactors allow direct control by PLC-output ≥ 24 V DC 500 mA and obtain a reduced holding coil
consumption. AF..Z contactors withstand short voltage dips and voltage sags (SEMI F47-0706 compliance)
between 24...250 V 50/60 Hz AF..Z contactors have built-in surge protection and do not require additional
surge suppressors The AF... series 1-stack 3-pole contactors are of the block type design. - Main poles and
auxiliary contact blocks: 3 main poles, 1 built-in auxiliary contact, front and side-mounted add-on auxiliary
contact blocks. (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1. N.C. mirror
contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: AC or DC operated - Accessories: a
wide range of accessories is available.
General Information
1 piece Minimum Order Quantity
85364900 Customs Tariff Number
Ordering
1SBC101402D0201 Data Sheet, Technical Information
1SBC101027M6801 Instructions and Manuals
Popular Downloads
45 mm Product Net Width
77 mm Product Net Depth / Length
86 mm Product Net Height
0.31 kg Product Net Weight
Dimensions
3 Number of Main Contacts NO
0 Number of Main Contacts NC
Technical
0 Number of Auxiliary Contacts NO
1 Number of Auxiliary Contacts NC
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1, UL 508, CSA C22.2 N°14 Standards
Auxiliary Circuit 690 V
Main Circuit 690 V
Rated Operational Voltage
Auxiliary Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Rated Frequency (f)
acc. to IEC 60947-4-1, Open Contactors q = 40 °C 35 A
acc. to IEC 60947-5-1, q = 40 °C 16 A
Conventional Free-air Thermal Current (Ith)
(690 V) 40 °C 25 A
(690 V) 60 °C 25 A
(690 V) 70 °C 22 A
Rated Operational Current AC-1 (Ie)
(220 / 230 / 240 V) 60 °C 9 A
(380 / 400 V) 60 °C 9 A
(415 V) 60 °C 9 A
(440 V) 60 °C 9 A
(500 V) 60 °C 9.5 A
(690 V) 60 °C 7 A
Rated Operational Current AC-3 (Ie)
(220 / 230 / 240 V) 2.2 kW
(380 / 400 V) 4 kW
(400 V) 4 kW
(415 V) 4 kW
(440 V) 4 kW
(500 V) 5.5 kW
(690 V) 5.5 kW
Rated Operational Power AC-3 (Pe)
(220 / 240 V) 4 A
(24 / 127 V) 6 A
(400 / 440 V) 3 A
(500 V) 2 A
(690 V) 2 A
Rated Operational Current AC-15 (Ie)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
for 0.1 s 140 A
for 1 s 100 A
Rated Short-time Withstand Current (Icw)
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Maximum Breaking Capacity
AC-1 600 cycles per hour
AC-15 1200 cycles per hour
AC-2 / AC-4 300 cycles per hour
AC-3 1200 cycles per hour
DC-13 900 cycles per hour
Maximum Electrical Switching Frequency
(110 V) 0.55 A / 60 W
(220 V) 0.27 A / 60 W
(400 V) 0.15 A / 60 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
(125 V) 0.55 A / 69 W
(24 V) 6 A / 144 W
(250 V) 0.27 A / 68 W
(48 V) 2.8 A / 134 W
(72 V) 1 A / 72 W
Rated Operational Current DC-13 (Ie)
acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Insulation Voltage (Ui)
6 kV Rated Impulse Withstand Voltage (Uimp)
3600 cycles per hour Maximum Mechanical Switching Frequency
50 Hz 24 ... 60 V
60 Hz 24 ... 60 V
DC Operation 20 ... 60 V
Rated Control Circuit Voltage (Uc)
Between Coil De-energization and NC Contact Closing 13 ... 98 ms
Between Coil De-energization and NO Contact Opening 11 ... 95 ms
Between Coil Energization and NC Contact Opening 38 ... 90 ms
Between Coil Energization and NO Contact Closing 40 ... 95 ms
Operate Time
2AF09Z-30-01-21
Flexible with Insulated Ferrule 1x 0.75 ... 4 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Flexible with Ferrule 1/2x 0.75 ... 6 mm²
Rigid 1/2x 1 ... 6 mm²
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Auxiliary Circuit 10 mm
Control Circuit 10 mm
Main Circuit 10 mm
Wire Stripping Length
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Degree of Protection
Screw Terminals Terminal Type
Close to Contactor for Storage -60 ... +80 °C
Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Ambient Air Temperature
Category B according to IEC 60947-1 Annex Q Climatic Withstand
3000 m Maximum Operating Altitude Permissible
5 ... 300 Hz 4 g closed position / 2 g open position Resistance to Vibrations acc. to IEC 60068-2-6
Closed, Shock Direction: B1 25 g
Open, Shock Direction: B1 5 g
Shock Direction: A 30 g
Shock Direction: B2 15 g
Shock Direction: C1 25 g
Shock Direction: C2 25 g
Resistance to Shock acc. to IEC 60068-2-27
Environmental
(600 V AC) 25 A General Use Rating UL/CSA
(120 V AC) Single Phase 3/4 Hp
(240 V AC) Single Phase 1-1/2 Hp
(200 ... 208 V AC) Three Phase 2 Hp
(220 ... 240 V AC) Three Phase 2 Hp
(440 ... 480 V AC) Three Phase 5 Hp
(550 ... 600 V AC) Three Phase 7-1/2 Hp
Horsepower Rating UL/CSA
Auxiliary Circuit 11 in·lb
Control Circuit 11 in·lb
Main Circuit 13 in·lb
Tightening Torque UL/CSA
Technical UL/CSA
ABS_15-GE1349500-PDA_90682247 ABS Certificate
BV_2634H24898B0 BV Certificate
CB_SE-80871M3 CB Certificate
CCC_2010010304445624 CCC Certificate
UL_20180227_E312527_7_1 cUL Certificate
1SBD250000U1000 Declaration of Conformity - CE
DNV-GL_TAE00001AF-3 DNV Certificate
DNV-GL_TAE00001AF-3 DNV GL Certificate
Certificates and Declarations (Document Number)
3AF09Z-30-01-21
EAC_RU C-FR ME77 B01010 EAC Certificate
1SBD250147E1000 Environmental Information
DNV-GL_TAE00001AF-3 GL Certificate
GOST_POCCFR.ME77.B07175.pdf GOST Certificate
1SBC101027M6801 Instructions and Manuals
KC_HW02016-15004A KC Certificate
LRS_1300087E1 LR Certificate
RINA_ELE084013XG RINA Certificate
RMRS_1802705280 RMRS Certificate
1SBD251013E1000 RoHS Information
UL_20140305-E312527_7_1 UL Certificate
E312527 UL Listing Card
1 piece Package Level 1 Units
87 mm Package Level 1 Width
79 mm Package Level 1 Depth / Length
47 mm Package Level 1 Height
0.31 kg Package Level 1 Gross Weight
3471523113312 Package Level 1 EAN
54 piece Package Level 2 Units
250 mm Package Level 2 Width
300 mm Package Level 2 Depth / Length
315 mm Package Level 2 Height
16.74 kg Package Level 2 Gross Weight
1296 piece Package Level 3 Units
Container Information
Q Object Classification Code
3210006 E-nummer
EC000066 - Magnet contactor, AC-switching ETIM 4
EC000066 - Magnet contactor, AC-switching ETIM 5
EC000066 - Power contactor, AC switching ETIM 6
EC000066 - Power contactor, AC switching ETIM 7
39121529 UNSPSC
Classifications
Low Voltage Products and Systems Control Products Contactors Block Contactors
Categories
4AF09Z-30-01-21
5AF09Z-30-01-21